The internal shielded
input transformer provides galvanic isolation with provisions for domestic (115
VAC, CONUS) and optionally for international (230 VAC, OCONUS) input
voltages. Special EMI/RFI filters and input
power factor correction minimize both input current and harmonics. This special
transformer and filters result in ultra low input leakage current required for
medical applications. The unit also operates
as a frequency converter, taking 46-440 hertz input and converting it to clean,
uninterruptible 60 hertz power. The input switch and the galvanic isolation
transformer all provide a double pole isolated source for
systems or locations where phase references and grounding are not
consistent. For scenarios that need hospital grade power immediately and
no AC source is available to run the UPS, the Cold Start pushbutton allows the unit to
start and run from its
battery modules before external AC is available.
Technical
Specifications: P/N: ETI0001-1260AA |
AC OUTPUT |
Output voltage: |
120 vac true sine-wave standard, others optional |
Output rating: UPS |
4000 va standard in 3U electronics chassis
0.65 to 0.75 pf standard, |
Non-linear load capacity: |
Up to 100% non-linear load capability w/o
de-rating |
Output voltage regulation: UPS |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: |
110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: |
Less than 5.0% into 100% non-linear load |
Output frequency: UPS |
60 or 50 Hz ± 2.5% synchronized to utility
60 or 50 Hz ± 1.0% w/ utility not available |
Operational status |
Status, load and battery level LEDs, w/contacts
Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT |
Input voltage selection: |
Nominal 115 vac, optional auto-ranging input of
85-270 vac |
Input voltage tolerance: UPS |
85-135 vac @ full load without using battery, to
70 vac @ 75% load |
Input frequency: |
From 46 hz to 70 hz standard, optional to 440 hz |
Input power factor: |
Better than 99% typically |
Input/output isolation: |
4000 va, up to 120 dB common mode, <1.0 ma
leakage |
Input transient suppression: |
Complies with IEEE 587 and UL 1449 |
Input control/protection: |
Guarded 2 pole input breaker w/ UPS fuses
Optional cold start to turn on w/o ac present |
Input power connection: |
MS3452W22-22P |
EXTERNAL BATTERY |
Battery type: |
Maintenance free immobilized electrolyte,
Flame retardant materials, Oxygen Index 28+ |
Battery life: |
Rated for continuous service life of 5 years |
DC protection: |
Panel mounted fuses standard, breaker optional |
Battery expansion: |
Up to 24 hours w/ Battery Expansion Modules |
DISTRIBUTION PANEL |
Output circuits: |
One output via solid-state relays |
Output control: |
Guarded Double Pole Circuit Breaker (CB2) |
Output receptacles: |
MS3452W22-22S |
MECHANICAL |
Dimensions ( H x D x W ): UPS
2U Battery Module |
5.25 (3U) x 23.5 x 19.0 in (133 x 597 x 483 mm)
3.50 (2U) x 23.5 x 19.0 in (89 x 597 x 483 mm) |
Rack Slide Mount Patterns: |
Jonathan, General Devices patterns standard,
others optional |
Alternate Mounting Options: |
Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: UPS
2U Battery Module |
95 lb. ( 43 kg) with lift handles
front and rear
105 lb. ( 48 kg) with lift handles front and rear |
Audible noise: |
Less than 47 dB @ 5.0 ft., ANSI "A"
scale |
Cooling type: |
High capacity, negative pressure, forced air |
Cooling air direction: |
Front intake, exhaust to rear, others optional |
Air intake filter: |
Washable metal filter media, others optional |
ENVIRONMENTAL |
Storage temperature: |
-40° to 158° F ambient (-40° to 70° C) |
Operating temperature: |
32° to 113° F ambient (0° to 45° C ), lower/
higher optional |
Operating humidity: |
0 to 95% relative humidity (non-condensing) |
Storage elevation: |
Up to 40,000 ft (12,192 m), higher optional |
Operating elevation: |
Up to 10,000 ft (3,048 m), higher optional |
STANDARDS |
United States: |
Meets UL-1778 standard for UPS equipment,
167-1, 454, 810D, 901D Grade A, 1399, Sec 300A & 2000 |
Canada: |
CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: |
EMI/RFI FCC Part 15, Class A; EN55022;
461 |
OPTIONAL ACCESSORIES |
|
Auto-ranging International Input, Cold Start,
Alternate I/O Configurations, Dual Source Input, Battery Expansion,
Battery-less Operation, Battery Charger/Conditioner, Power Distribution
Units, Software Interface, Asynchronous serial COM port, 10BaseT
Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits |