Part Number: ETI0001-2275
Rugged Rack or Fixed Mount
2000 VA UPS & Frequency Converter
1400 Watt (1.9 Hp) Commercial/Industrial
2 kVA UPS with a Variety of Power Levels Available
& Frequency Converter used in Shelters and Wind Turbine
Applications.
Rugged Rack or Fixed Mount Unit w/ Reduced Depth and
Removable Low Cost Battery Module

ETI0001-2275 Rugged UPS Standard Front Panel Layout

ETI0001-2275 Rugged UPS Standard Right Panel Layout
The field proven PowerStation UPS line is ideally
suited for industrial, computer, military, and telecommunications
applications requiring high reliability, rugged construction,
compact size and light weight design. These units are equally
suited for use in shipboard, airborne, vehicular, field
deployed or fixed locations with controlled or uncontrolled
environments. The "ETI0001-2275" is being used
a because of their stringent performance and reliability
requirements.
The heavy-duty chassis, occupying only 6.967" (4U)
of rack space and 15.68" depth, has rounded metal corners
and rugged handles right and left, aiding in safe handling.
Internally, all major components are well secured and electrically
insulated to prevent damage due to shock and vibration.
The internal shielded input transformer provides galvanic
isolation with provisions for domestic (120 VAC, CONUS)
and optionally for international (230 VAC, OCONUS) input
voltages. Special EMI/RFI filters and input power factor
correction minimize both input current and harmonics. The
unit also operates as a frequency converter, taking 46-70
hertz input and converting it to clean, uninterruptible
60 hertz power. The input switch and the galvanic isolation
transformer all provide a double pole isolated source
for shipboard systems or overseas locations where phase
references and grounding are not consistent.
The LED arrays keep the operator informed as to the unit's
status including load and battery levels. The high intensity
audible alarm can be heard in high noise environments. All
controls and protective devices are brought to the front
and rear panels with critical switches having finger guards.
Further, all front panel devices are recessed to prevent
damage or accidental operation. Various optional power distribution
controls are available which mount on the front panel or
remotely.
The right panel provides locking connectors for the input
and output power. Multiple input and output power panel
options are available. Removable and washable air filters
and a high capacity stainless steel ball bearing fans provide
added protection in both controlled and hostile environments.
The exhaust air is diverted out the rear vent, with alternate
air flow directions optional. The batteries are maintenance
free with immobilized electrolyte and are constructed of
flame retardant materials. For more information, see the Battery
Technology section. The Status connector provides
an interface with optional computer software providing
loss of AC and low battery status as well as remote shut
down capability.
See the Power
Distribution Units section for a listing of stand
alone PDUs. See the N5 Series ETI0001-1482 for
a version of this UPS with an integrated PDU and remote
control.
Overall, the PowerStation line is uniquely qualified for
critical shipboard, vehicle, airborne or land based systems
combining advanced modular design features with highly reliable
construction. |
Technical Specifications: P/N:
ETI0001-2275
| AC INPUT |
| Nominal voltage: UPS |
Nominal 120 VAC, optional autoranging
input of 85-270 VAC |
| Voltage Range: UPS |
85-140
VAC @ full load without using battery, to 70 VAC @
75% load |
| Current (max): UPS |
14A |
| Frequency: UPS |
From 50 Hz to 60 Hz standard,+/_5% |
| Efficiency: UPS |
>86% |
| Power Factor: UPS |
>0.95% |
| AC
OUTPUT |
| VA rating: |
2000 VA |
| Power Factor (Resistive Load) |
1400 W |
| Voltage (Selectable): |
110 V |
| 115 V |
| 120 V |
| Frequency: |
50/60 Hz (auto tracking) |
| Voltage Regulation: |
+/_ @% |
| Frequency Stability: |
+/_ 0.3% (Battery mode) |
| Step Load Change: |
+/_ 7% for 100% Load Variation |
| Harmonic Distortion: |
Linear Load <3%
Non-Linear Load <5% |
| Overload |
105% load for 50 seconds |
| Crest Ratio |
3:1 |
| INTERNAL
BATTERY |
| DC Voltage |
72V |
| Type |
12V, 7AH Sealed Lead Acid |
| Backup Time |
Full Load: 7 min. typ.
Half Load: 20 min. typ. |
| Recharge Time |
8 Hours to 90% |
| Transfer
Time |
| Line Fails/Recovers |
Zero Time - True online,
no transfer for brownoutor blackout |
| UPS- Bypass/Reverse |
<4 ms for bypass transfers |
| After Overload |
Auto Transfer to UPS |
| Audible Noise |
@ 1 Meter |
<_55dBA |
| Indicators |
L.E.D. |
Line, Inverter, Battery Reserve, Load, Bypass, Alarm,
Crest, Battery & Load Capacity Level |
| Audible Alarms |
|
DC Mode, Low Battery, Over/Under Voltage,
Over/Under Frequency, High Temperature, Over Load,
Alarm. |
| Interface |
Computer |
RS-232 (Supports RUPSII, UPSILON & SEC
protocols) |
| Environment |
| Temperature |
0°C-40°C (32°F
- 104°F) |
| Humidity |
10% - 95% Non-condensing |
| MECHANICAL |
| Input Line 120V |
6 Foot Cord with NEMA L5-20
Plug |
| Output 120V |
(2) NEMA 5-15R, (1) CPC,
PNL, SOC, S3, 17-3 |
Unit weight: |
68.4 lb. (31kg) |
| Approvals |
Agency |
UL, CUL, FCC Class A, (CE on specified
models only) |
| OPTIONAL
ACCESSORIES |
| |
Autoranging International
Input, Cold Start, Emergency Power Off, Elapsed Time
Meter, Alternate I/O Configurations, Dual Source Input, Battery
Expansion, Batteryless Operation, Battery
Charger/Conditioner, Power
Distribution Units, Software
Interface, Asynchronous serial COM port,
10BaseT Ethernet SNMP/HTTP port, Transport
Cases, Slides
and Mounting Kits |
1) European CE Certification
Only.
2) Isolation Transformer.
3) Backup time is for reference only. Actual duration
may vary depending on temperature, battery condition
and type of load.
4) Contact Factory for 120V settings.
5) Factory Default Settings.
|
|
|
|
|
 |
|
 |
|