Part Number: ETI0001-1240AD
Rugged Rack or Fixed Mount 1000 VA UPS
with 461E Surface, Shock Vibration,
Operational to 70° C
with Remote ON/OFF
US Air Force ECMO Medical Patient Cart
Application
1.0 kVA UPS and Frequency Converter
w/ Reduced Depth
Accepts both Aircraft Power and Commercial Power

ETI0001-1240AD Rugged UPS Standard Front Panel Layout,
Shown w/ Rack Flanges Mounted

ETI0001-1240AD Rugged UPS Standard Rear Panel Layout
The field proven PowerStation™ UPS line is ideally suited for military, industrial, medical and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The "ETI0001-1240AD" is being used by the US Air Force ECMO Cart project because of their stringent performance and reliability requirements.
The heavy-duty chassis, occupying only 3U (5.25") of rack space and 18.5" depth, has rounded metal corners and rugged handles front and rear, aiding in safe handling. Companion 2U (3.5" high) Battery Expansion Modules are designed to be daisy chained to bring the backup time to 4 hours in the typical configuration. In the typical ECMO Cart application, the base UPS unit and up to four Battery Modules are mounted in the lower underside section of the patient cart. Both module chassis are constructed of brushed aluminum to minimize overall weight. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration.
The internal shielded input transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optionally for international (230 VAC, OCONUS) input voltages. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. This special transformer and filters result in ultra low input leakage current required for medical applications. The unit also operates as a frequency converter, taking 46-440 hertz input and converting it to clean, uninterruptible 60 hertz power. The input switch and the galvanic isolation transformer all provide a double pole isolated source for systems or locations where phase references and grounding are not consistent. For scenarios that need hospital grade power immediately and no AC source is available to run the UPS, the Cold Start pushbutton allows the unit to start and run from its battery modules before external AC is available.
The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to the front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. Various optional power distribution controls are available which mount on the front panel or remotely.
The rear panel provides a locking connector for the input power and four hospital grade NEMA 5-15R output receptacles. Multiple input and output power panel options are available. Removable and washable air filters and a high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments. The exhaust air is diverted out the front vent, with alternate air flow directions optional. The "ETI0001-1240AD" has the added benefit of having both an internal battery and external battery expansion modules. The external Battery Modules can be field replaced without having to shut the UPS down. This allows the backup time to be extended even further. The optional Battery Charger/Conditioner (which has aircraft and global input capability) is used to maintain the spare Battery Modules in ready condition at all times. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
See the Power Distribution Units section for a listing of stand alone PDUs. See the N5 Series ETI0001-1479 for a version of this UPS with an integrated PDU and remote control.
Overall, the PowerStation line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
AC OUTPUT | |
Output voltage: UPS | 120 vac true sinewave standard, up to 600 vac optional |
Output rating: UPS | 1000 va standard in 3U x 18.5" deep 0.65-0.75 pf standard |
Non-linear load capacity: UPS | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: UPS | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: UPS | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 Hz ± 1.0% independent of input frequency |
Operational status | Status, load and battery LEDs,
w/contacts |
AC INPUT | |
Input voltage selection: | Auto Ranging Input 85-270VAC |
Input voltage tolerance: UPS | 85-270VAC @ full load without using battery, to 70 vac @ 75% load |
Input frequency: | From 46 hz to 70 hz standard |
Input power factor: | Better than 99% typically |
Input/output isolation: | 1000 va, up to 120 dB common mode, <700 microampere leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole switch w/ fuse, |
Input power connection: | MS 3102A-22-2P, 3 pin, threaded locking |
EXTERNAL BATTERY (Optional) | |
External battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
External battery life: | Rated for continuous service life of 5 years |
External DC protection: | Front panel mounted fuse standard |
External battery recharge: | Recharged to nominal in <8 hours |
DISTRIBUTION PANEL | |
Output circuits: | Four Output's |
Output receptacles: | MS3102R22-2S, 3 pin, threaded locking |
MECHANICAL | |
Dimensions ( H x D x W ): UPS |
5.25 (3U) x 18.5 x 19.0 in |
Mount Patterns: | Table Top |
Alternate Mounting Options: | Rack Mount, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: UPS base unit only |
95 lb. (34 kg) UPS with lift handles front and rear |
Cooling type: | High capacity, positive pressure, forced air |
Cooling air direction: | Rear intake, exhaust to Front |
Air intake filter: | EMI screen |
ENVIRONMENTAL | |
Storage temperature: | -40° to 158° F ambient (-40° to 70° C) |
Operating temperature: | 32° to 158° F ambient ( 0° to 70° C), lower/ higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m), higher optional |
Operating elevation: | Up to 10,000 ft (3,048 m), higher optional |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, 167-1, 454, 810D, 901D Grade A, 1399, Sec 300A & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC Part 15, Class A; EN55022; 461 |
OPTIONAL ACCESSORIES | |
Emergency Power Off, Elapsed Time Meter, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port, Slides and Mounting Kits |